Voltage Drop Calculator

Voltage lost along a copper wire run by AWG size, current and length — in volts and percent, checked against the 3% target.

—

Voltage drop

Drop as percent—
Voltage at the load—
Verdict—

Note: Copper conductors at standard reference resistance, DC or single-phase AC resistive loads. Aluminium wire drops about 1.6× more for the same gauge.

Report a problem with this tool

Voltage Drop: The Invisible Tax on Long Wires

Every wire resists a little, so some voltage is spent along the run and the load sees less than the source sent. For a DC or single-phase circuit the drop is 2 × length × current × resistance per unit length — the 2 because the current makes a round trip. This calculator uses standard copper resistance values per AWG size and reports the drop in volts and as a percentage, the figure wiring rules actually judge: under 3% for a branch circuit is the usual target.

Worked Example

A 120 V circuit drawing 10 A over a 50 ft one-way run of 12 AWG copper (1.588 Ω per 1,000 ft): drop = 2 × 50 × 10 × 1.588 / 1,000 = 1.59 V, which is 1.32% — comfortably inside target, and the load sees 118.41 V. Stretch the run to 200 ft and the same load drops 6.35 V (5.3%): lights dim, motors run hot, and the fix is a thicker wire, not a bigger breaker.

Why Low Voltage Suffers Most

The drop depends on current and wire, not on system voltage — but the percentage does. The same 1.59 V lost from a 12 V solar run is 13% of everything, which is why off-grid and automotive wiring uses startlingly thick cable for modest currents. When a calculator result surprises you, it is usually this ratio talking.

Frequently Asked Questions

What voltage drop is acceptable?

The usual targets are 3 percent for a branch circuit and 5 percent for the whole run including the feeder. The result panel checks your figure against the 3 percent branch target.

Why does the formula multiply by 2?

Current travels out on one conductor and back on the other, so the run length that matters is twice the one-way distance. Forgetting the 2 is the most common voltage-drop error.

How do I fix an excessive drop?

Thicker wire (a lower AWG number), a shorter run, or less current. Doubling the wire cross-section roughly halves the drop; a bigger breaker does nothing for it.

Why do 12 V systems need such thick cable?

The drop in volts is the same, but as a percentage of 12 V it is ten times worse than on 120 V. Low-voltage runs are governed by percentage, so their cables grow.